Catálogo
Warning! You must be logged in to download documents. If not, you will be redirected to the login page

SÉRIE ADVANCE-GRP[<50V]

TOMADA BLOQUEADA

Cod. 503.2416-F

16A 2P 24V II 3D Terminais de parafuso Con enclavamiento eléctrico

Série comercial
Série ADVANCE-GRP[<50V]
Descrição sintéica
TOMADA BLOQUEADA
Corrente nominal
16A
Polos
2P
Tensão nominal (range)
0-50V
Tensão nominal
24V
Cor
ROXO
Material
GRP Glass Reinforced Polyester
Grau de proteção
Splash proof
Grau de proteção IP
IP66
Grau de proteção IK
IK10
Conector borne
Terminais de parafuso
Material de contacto
CuZn (latão)
Working temperature
-40°C/+60°C
GLOW WIRE
GW 960°C
Auto-extinguível UL94
V0
Group and categories EX
II 3D
modo de proteção poeira
Ex tc IIIC T90°C Dc IP66
Ambient temperature Ta min
-25 °C
Ambient temperature Ta max
60 °C
Opções
Con enclavamiento eléctrico
Notas
CON TRASFORMATORE 120VA
Catalogue notes
Lado em branco com marca de ponto de perfuração
Fusíveis não fornecidos
Transformador SELV 220/24V~ 150VA (serviço contínuo).

Product

EAN code
8001636238005
INTRASTAT code
8536699099
Net weight
5.861 KG
Quantidade Mínima
1

Packaging

Packaging Carton
EAN code
Quantity
1
Depth
515.0 MM
Width
140.0 MM
Height
180.0 MM
Volume
12978.0 CCM
EN 60309-1/A1 (2007) [European Standard] Plugs, socket-outlets and couplers for industrial purposes. Part 1: General requirements
EN 61558-1/A11 (2003) [European Standard] Safety of power transformers, power supply units and similar. General requirements and tests
EN 60309-2/A1 (2007) [European Standard] Plugs, socket-outlets and couplers for industrial purposes. Part 2: Dimensional interchangeability requirements for pin and contact-tube accessories of harmonized configurations
EN 61558-2-6 (1997) [European Standard] Safety of transformers, reactors, power supply units and similar products for supply voltages up to 1 100 V - Part 2-6: Particular requirements and tests for safety isolating transformers and power supply units incorporating saf[...]..
EN 61558-1 (1997) [European Standard] Safety of power transformers, power supply units and similar. General requirements and tests
EN 60309-2/A2 (2012) [European Standard] Plugs, socket-outlets and couplers for industrial purposes. - Part 2: Dimensional interchangeability requirements for pin and contact-tube accessories of harmonized configurations
EN 60309-1/A2 (2012) [European Standard] Plugs, socket-outlets and couplers for industrial purposes. - Part 1: General requirements
EN 61558-1/A1 (1998) [European Standard] Safety of power transformers, power supply units and similar. General requirements and tests
EN 60309-2 (1999) [European Standard] Plugs, socket-outlets and couplers for industrial purposes. Part 2: Dimensional interchangeability requirements for pin and contact-tube accessories of harmonized configurations
DIRECTIVE ATEX 2014/34/UE [European Directives] Atmosphere Explosive
EN 60079-0 (2012) [European Standard] Explosive atmospheres. General requirements.
EN 60309-1 (1999) [European Standard] Plugs, socket-outlets and couplers for industrial purposes. Part 1: General requirements
DIRECTIVE EMC 2014/30/UE [European Directives] Electromagnetic Compatibility Directive
EN 60079-0/A11 (2013) [European Standard] Explosive atmospheres. General requirements.
EN 60079-31 (2014) [European Standard] Explosive atmospheres. Equipment dust ignition protection by enclosure "t"
DIRECTIVE LOW VOLTAGE 2014/35/UE [European Directives] Low Voltage Directive
thumbnail
SCAME Ex
ATEX
thumbnail
UKCA marking
UK Conformity Assessed
thumbnail
UE
Declaratiòn de conformidad
thumbnail
EAC
Eurasian Conformity
Você precisa da Folha Técnica do produto ?
Baixe em formato pdf
Você precisa de Documentação ou Certificação do produto ?

Tem o número de série do seu produto ?

Você precisa de Documentação ou Certificação do produto ?

Aprofundamento

Scame Parre S.p.a
Via Costa Erta 15
24020 Parre (BG) -  Italy
Tel. 
Via Costa Erta 15
24020 Parre (BG) -  Italy

© 2023 Scame Parre S.p.a. - VAT IT00137900163