SÉRIE ADVANCE-GRP[GD]

PRISE VERROUILLABLE

Cod. 504.16832-A

16A 2P+T 2h >50V >300-500Hz II 2GD 130X260MM_PAR Bornes à vis Avec verrouillage mécanique Low temperature [-50°C]

Série commerciale
Série ADVANCE-GRP[GD]
Description
PRISE VERROUILLABLE
Type de installation
MONTAGE SAILLIE
Courant nominal
16A
Pôles
2P+T
Position d'heure
2h
Tension nominale
>50V
Fréquence d'utilisation
>300-500Hz
Couleur
ROUGE
Matériau
GRP Glass Reinforced Polyester
Indice de protection
Splash proof
Indice de protection IP
IP66
Indice de protection IK
IK10
Bornes
Bornes à vis
Matériel de contact
CuZn (laiton)
Plastron
130X260MM_PAR
Sortie du câble
1xM25
Température de fonctionnement
-40°C/+60°C
Fil incandescent
960°C
Autoextinguible UL94
V0
Groupe et catégories EX
II 2GD
Température ambiante Ta min
-50 °C
Température ambiante Ta max
60 °C
Options
Avec verrouillage mécanique
Low temperature [-50°C]
Cadenas
ø5mm
Catalogue notes
ATEX [ATmosphères EXplosibles]: pour les applications dans des atmosphères potentiellement explosives.

Product

EAN code
8001636088266
INTRASTAT code
8536699099
Net weight
0 KG
Quantité minimum
1
EN 60309-1/A1 (2007) [European Standard] Plugs, socket-outlets and couplers for industrial purposes. Part 1: General requirements
EN 60079-1 (2014) [European Standard] Electrical apparatus for explosive gas atmospheres - Part 1: Flameproof enclosures 'd'
EN 60079-0 (2018) [European Standard] Explosive atmospheres. General requirements.
EN 60309-1/A2 (2012) [European Standard] Plugs, socket-outlets and couplers for industrial purposes. - Part 1: General requirements
EN 60309-2 (1999) [European Standard] Plugs, socket-outlets and couplers for industrial purposes. Part 2: Dimensional interchangeability requirements for pin and contact-tube accessories of harmonized configurations
DIRECTIVE ATEX 2014/34/UE [European Directives] Atmosphere Explosive
EN 60309-1 (1999) [European Standard] Plugs, socket-outlets and couplers for industrial purposes. Part 1: General requirements
EN 60079-7 (2018) [European Standard] Explosive atmospheres. - Part 7: Equipment protection by increased safety "e"
EN 60079-7 (2015) [European Standard] Explosive atmospheres. Equipment protection by increased safety "e"
thumbnail
INERIS Atex
Institut National de l'Environnement Industriel et des Risques
thumbnail
INERIS IECEx
Institut National de l'Environnement Industriel et des Risques
thumbnail
UKCA marking [EUROFIN UKCA ATEX]
UK Conformity Assessed
thumbnail
UKCA marking
UK Conformity Assessed
thumbnail
UE
Déclaration de conformité
thumbnail
Notifica ATEX
Product quality assurance notification
thumbnail
Notifica ATEX
Product quality assurance notification
Avez-vous besoin de la fiche technique du produit au format pdf et imprimable?
Télécharger la Fiche Technique
Vous avez besoin de documentation technique, de manuels, de fiches d’instructions ou de certificats ?

Avez-vous le numéro de série de votre produit ?

Avez-vous besoin de visualiser le produit en 3D ?

Approfondissements

Produits connexes

Scame Parre S.p.a
Via Costa Erta 15
24020 Parre (BG) -  Italy
Via Costa Erta 15
24020 Parre (BG) -  Italy

© 2023 Scame Parre S.p.a.